Ancillary Systems

Plant specification

Newell WTP

Newell Regional Services Corp. (NRSC) · Brooks, AB, Canada

Status not reported
Pall/Aria Microza microfiltration (MF)
Source: Lake Newell Reservoir
OEM: Pall (now AriaFiltra)
OEM: Kinetico

Clean-in-place (CIP) system

Tank capacity
3,000 US gal (11.4 m³)
Solution reuse
Up to 2×
Functions
  • acid wash
  • caustic wash
  • rack rinse
  • acid recovery
  • caustic recovery
  • timed soak
  • acid/caustic solution preparation
  • solution reuse/validity
  • neutralization
Chemicals
  • sodium hypochlorite
  • sodium hydroxide
  • citric acid
  • sodium bisulfite

2026 CIP strainer failure

Failed unit
4-in Spears YS33P20-040 (plastic basket/screen)
Replacement ordered
Spears YS23S30-040 — 4-in flanged PVC, 316 SS #30 mesh screen, EPDM O-ring
Replacement rating
90 psi at 73 °F; max 140 °F (60 °C)
CIP pump discharge
240 kPa
CIP temperature (max)
38 °C
Lesson
Nameplate pressure/temperature alone does not define the operating envelope; differential pressure across a plugged strainer can be the governing load. Adding upstream/downstream gauges or a DP transmitter is warranted.
CIP spare parts →

Compressed air

As recorded in the 2020 inspection

UnitModelRun hours (2020)Load / unload (psi)
AAtlas Copco GA30VSD+8,123132 / 140–147
BAtlas Copco GA30VSD+7,644120 / 130–136
Integrity-test regulator target
27–30 psi
Integrity-test regulator minimum
25 psi
Pneumatics spare parts →

Integrity testing

Automated, built into Pall system

2020 finding — PIT-1021 (filtrate pressure transmitter used in IT measurement)
Debris accumulation affecting IT pressure readings. Operator response: reportedly bled ~weekly.
Test depends on
  • clean pressure sensing
  • correct IT regulator pressure
  • leak-free module connections
  • reliable valve seating
  • proper instrument calibration