DEMODemonstration build · sample data is marked · not connected to live plant systems

Controls

Plant specification

Newell WTP

Newell Regional Services Corp. (NRSC) · Brooks, AB, Canada

Status not reported
Pall/Aria Microza microfiltration (MF)
Source: Lake Newell Reservoir
OEM: Pall (now AriaFiltra)
OEM: Kinetico
2026 status
As of 2026-09-08, Newell has been given Aria's budgetary proposal for a controls refurbishment; the legacy control system is now part of the plant's lifecycle envelope, not just an operating condition

Control system

Architecture
Allen-Bradley ControlLogix, with redundant processors added in a later modification
Distributed I/O
Numatics G2 distributed pneumatic/I/O manifolds
HMI / SCADA
Pall HMI/SCADA interface
Networks
  • ControlNet
  • DeviceNet
Controls spare parts →
2020 inspection findings
  • PLC program not stored on the plant PC
  • Rockwell software/code reportedly held by MPE
  • Electrical drawings missing from several panels
  • One air-scrub flow signal had a substantial HMI delay from being routed through the plant PLC instead of directly to the Pall MCP